新闻中心

NEWS

可蓝新风系统

Key Factors When Choosing a Gel-Seal HEPA Filter

2025-06-14 20:43:09

Click:

“ Choosing a gel-seal HEPA filter requires a balanced review of efficiency, sealing design, dimensions, environment, resistance, maintenance, and lifecycle cost. ”
When selecting a gel-seal HEPA filter, consider filtration performance, structural design, operating conditions, and other factors together to ensure efficiency, reliability, and economy.
Filtration Efficiency and Grade Certification

1. Match the Efficiency Grade to the Requirement

Core indicator: Under ISO 16890 or EN 1822, high-efficiency filters commonly include grades H13, at least 99.97% at 0.3 μm; H14, at least 99.995% at 0.3 μm; and U15, at least 99.9995% at 0.12 μm. Select the grade for the application. For example:

Pharmaceutical cleanrooms and electronics workshops require H14 or above to control fine-particle contamination.

Laboratories and biosafety cabinets can use H13 for basic high-efficiency filtration.

Test standard: Confirm that the filter has passed a DOP, dioctyl phthalate, or PAO, polyalphaolefin, test so its actual efficiency is verified.

2. Industry Compliance Certification

Pharmaceutical and food applications must meet GMP requirements, while electronics applications must meet SEMI standards. The filter should be supplied with a third-party test report, such as one from a CNAS-accredited laboratory.

Gel-Seal Design and Performance

1. Seal Channel Structure and Material

Channel material: Prefer corrosion-resistant aluminum alloy or 304 stainless steel to prevent rust during long-term use and avoid chemical reactions with the sealing liquid.

Channel depth and width: Standard seal channels are generally at least 25 mm deep, providing enough sealing liquid without easy overflow. The fit tolerance between the frame and channel should be no more than 0.5 mm to prevent leakage through gaps.

2. Sealing-Liquid Properties

Temperature resistance: Select for the operating temperature. A mineral-oil-based sealing liquid is suitable for normal environments up to 40°C. High-temperature applications such as oven exhaust require a silicone-based sealing liquid rated for at least 200°C.

Volatility and toxicity: Cleanrooms require a low-volatility, nontoxic sealing liquid, such as food-grade white oil, to avoid contaminating the environment or product.

Flow and freezing point: The sealing liquid must remain liquid from -10°C to 80°C. Freezing at low temperature or evaporation at high temperature can cause seal failure.

Dimensional and Frame Compatibility

1. Match the Installation Dimensions

Filter dimensions must match the ventilation duct, plenum, or filter frame precisely. Common standard sizes include 610 x 610 x 292 mm and 1,220 x 610 x 292 mm; nonstandard sizes require customization. Also check the frame interface, such as a knife-edge or slot design, to ensure it matches the filter's gel-seal installation method. A structural mismatch can cause seal failure.

2. Frame Strength and Corrosion Resistance

Prefer aluminum alloy for low weight and corrosion resistance, or galvanized steel for low cost. In humid locations such as hospital operating rooms, use a 316 stainless-steel frame to prevent rust from damaging the seal.

Adaptability to the Operating Environment

1. Temperature and Humidity Range

Temperature: A standard filter is suitable for temperatures up to 80°C. A high-temperature environment requires heat-resistant sealing liquid and a suitable frame, such as a silicone-rubber seal with a stainless-steel frame.

Humidity: In environments at or above 80% relative humidity, check the moisture resistance of the filter paper. Fiberglass paper with a waterproof coating can help prevent moisture damage and tearing.

2. Compatibility with Special Gases

If acid mist, organic solvents, or other corrosive gases are present, select a chemically resistant filter, such as a PTFE-coated frame with a fluoroelastomer seal, to prevent corrosion of the frame or filter paper.

Resistance and Dust-Holding Capacity

1. Resistance Control

Initial resistance: At rated airflow, the initial resistance of an H13 filter is generally no more than 250 Pa, and that of an H14 filter no more than 300 Pa. Excessive resistance increases fan energy consumption.

Final resistance: The final value is generally set at 2-2.5 times initial resistance. For example, H13 final resistance should be no more than 500 Pa. Match this value to the available fan pressure to prevent insufficient airflow.

2. Dust-Holding Capacity and Service Life

A filter with dust-holding capacity of at least 400 g/m² is better for dusty environments such as industrial workshops. It extends the replacement interval and reduces maintenance cost.

Monitor resistance regularly. Replace the filter when it reaches final resistance to prevent overload from reducing efficiency or damaging the filter paper.

Ease of Installation and Maintenance

1. Error-Proofing and Installation Guidance

The filter should have an airflow-direction arrow to prevent reverse installation and a sharp loss of efficiency. The gel-seal frame should have locating slots to prevent displacement during installation.

2. Sealing-Liquid Maintenance

Some sealing liquids require regular level checks, such as quarterly inspections. Refill promptly when the liquid falls below the minimum mark to prevent leakage due to insufficient volume.

When replacing a filter, remove residual sealing liquid from the channel so old and new liquids do not mix and impair performance.

Cost and Lifecycle Assessment

1. Initial Purchase Cost

An H14 filter costs about 1.5-2 times as much as an H13 filter. Balance value against the required cleanliness grade to avoid wasting money on an unnecessarily high grade.

Calculate total cost over the replacement cycle, including purchase, energy, and maintenance costs. For example:

A high-dust-capacity filter costs more initially but requires less frequent replacement, making it suitable for systems that operate for long periods.

A low-resistance filter may cost slightly more initially but can reduce fan energy consumption, making it suitable for large ventilation systems.
0
Key Factors When Choosing a Gel-Seal HEPA Filter
Choosing a gel-seal HEPA filter requires a balanced review of efficiency, sealing design, dimensions, environment, resistance, maintenance, and lifecycle cost.
Long by picture save/share

 

Company landline

010-60770969

Sales Phone/WeChat: 15601000090

Purchasing Management/WeChat: 13331060986

Company Phone: 010-60770969

Address: Room 1708, Building B, Jinyu International Center, Longyu East 1st Road, Huilongguan Street, Changping District, Beijing

©2026 Kelan Filtration Technology(Beijing) Group Co., Ltd. All rights reserved

Record Number: Jing ICP No. 2022016037-2

Technical Support: Suyuan Network

 

Sales Phone/WeChat: 15601000090

Purchasing Management/WeChat: 13331060986

Company Phone: 010-60770969

Address: Room 1708, Building B, Jinyu International Center, Longyu East 1st Road, Huilongguan Street, Changping District, Beijing

©2026 Copyright Beijing Kelan Fresh Air Technology Co., Ltd. All rights reserved

Record Number: Jing ICP No. 2022016037-2 

Technical Support: Suyuan Network

Service Center
Contacts
Product Sales :
15601000090
Procurement Management :
13331060986
Company Landline :
010-60770969
Qrcode
Qrcode
WeChat (scan to add)
Service Center
Add WeChat friend to learn more about the product
Use Enterprise WeChat
"Scan" to join the group chat
Copy success!
Add WeChat friend to learn more about the product
I see.